| Assessment Year | 2003 |
|---|---|
| Principal Product | Electrical connectors |
| NAICS | 325414: Biological Product (except Diagnostic) Manufacturing |
| SIC | 3643: Current-Carrying Wiring Devices |
| Sales Range | $50 M to 100M |
| # of Employees | 206 |
| Plant Area |
130,000
ft2
|
| Annual Production | 5,000,000
pieces
|
| Production Hrs. Annual | 6,120
hrs
|
| Location (State) | New Hampshire |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $193,460 | 3,562,800 |
kWh
|
$0.054 |
| Electricity Demand | $90,081 | 10,156 |
kW-mo/yr
|
$8.87 |
| Electricity Fees | $544 | - |
|
- |
| Fuel Oil #2 | $35,148 | 4,663 |
MMBtu
|
$7.54 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $41,175 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,855 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $18,973 | $48,190 |
$23,872
439,636
kWh
|
$8,301
-
kW-mo/yr
|
$(-13,200.0)
-
MMBtu
|
|
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $9,180 | $16,000 | - | - |
$9,180
-
MMBtu
|
|
| 03 | 2.2437: Recover waste heat from equipment | $7,167 | $9,862 | - | - |
$7,167
-
MMBtu
|
|
| 04 | 2.7221: Lower temperature during the winter season and vice-versa | $3,752 | - | - | - |
$3,752
-
MMBtu
|
|
| 05 | 2.7135: Install occupancy sensors | $2,103 | $1,325 |
$2,103
38,738
kWh
|
- | - | |
| TOTAL RECOMMENDED | $41,175 | $75,377 |
$25,975
478,374
kWh
|
$8,301
-
kW-mo/yr
|
$6,899
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $5,855 | $1,325 |
$2,103
38,738
kWh
|
- |
$3,752
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs