Assessment Year | 2000 |
---|---|
Principal Product | Injection Molding Plastic Products |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 142 |
Plant Area |
78,468
ft2
|
Annual Production | 2,700
ton
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $241,226 | 5,665,229 |
kWh
|
$0.043 |
Electricity Demand | $131,789 | 10,868 |
kW-mo/yr
|
$12.13 |
Electricity Fees | $4,437 | - |
|
- |
LPG | $755 | 69 |
MMBtu
|
$10.94 |
Fuel Oil #1 | $6,279 | 1,357 |
MMBtu
|
$4.63 |
Fuel Oil #2 | $8,787 | 1,901 |
MMBtu
|
$4.62 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $76,598 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $72,242 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
---|---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $28,890 | $140,000 |
$22,578
459,555
kWh
|
$6,312
-
kW-mo/yr
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $24,924 | $129,000 |
$15,718
313,013
kWh
|
$9,206
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,760 | $1,200 |
$5,760
117,233
kWh
|
- | - | |
04 | 2.6212: Turn off equipment during breaks, reduce operating time | $5,180 | - |
$5,180
89,097
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,269 | $350 |
$3,269
66,530
kWh
|
- | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,779 | $7,000 |
$2,779
56,565
kWh
|
- | - | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $2,770 | $100 |
$2,060
41,911
kWh
|
$710
-
kW-mo/yr
|
- | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,440 | $3,000 |
$1,440
29,308
kWh
|
- | - | |
09 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $936 | $5,000 |
$821
16,706
kWh
|
$781
-
kW-mo/yr
|
$(-666.0)
-
MMBtu
|
|
10 | 2.4221: Install compressor air intakes in coolest locations | $650 | $1,250 |
$650
13,189
kWh
|
- | - | |
TOTAL RECOMMENDED | $76,598 | $286,900 |
$60,255
1,203,107
kWh
|
$17,009
-
kW-mo/yr
|
$(-666.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $72,242 | $280,550 |
$56,724
1,131,301
kWh
|
$15,518
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs