| Assessment Year | 1994 |
|---|---|
| Principal Product | commercial, xerox, business, social and specialty industrial |
| NAICS |
n/a
|
| SIC | 2621: Paper Mills |
| Sales Range | $10 M to 50M |
| # of Employees | 129 |
| Plant Area |
323,250
ft2
|
| Annual Production | 20,000
ton
|
| Production Hrs. Annual | 6,600
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,797,345 | 22,723,037 |
kWh
|
$0.079 |
| Natural Gas | $277,708 | 112,475 |
MMBtu
|
$2.47 |
| Fuel Oil #6 | $243,680 | 104,038 |
MMBtu
|
$2.34 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $82,792 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $82,792 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4314: Use synthetic lubricant | $30,227 | $8,568 |
$30,227
382,181
kWh
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $37,969 | $30,800 |
$37,969
480,070
kWh
|
|
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $12,749 | - |
$12,749
161,196
kWh
|
|
| 04 | 2.7424: Shade windows from summer sun | $1,847 | $5,000 |
$1,847
23,447
kWh
|
|
| TOTAL RECOMMENDED | $82,792 | $44,368 |
$82,792
1,046,894
kWh
|
||
| TOTAL IMPLEMENTED | $82,792 | $44,368 |
$82,792
1,046,894
kWh
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs