Assessment Year 1994
Principal Product Seals, Valves, Tensioners, and Bellows
NAICS
n/a
SIC 3053: Gaskets, Packing, and Sealing Devices
Sales Range $10
M
to 50
M
# of Employees 180
Plant Area 96,000
ft2
Annual Production 0
units
Production Hrs. Annual 5,200
hrs
Location (State) Rhode Island

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $247,699 2,038,394
kWh
Natural Gas $5,090 784
MMBtu
Fuel Oil #2 $7,255 1,728
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $60,944 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $33,663

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings Fuel Oil #2 Savings Water Consumption Savings
01 2.2612: Use cooling tower water instead of refrigeration $19,139 $8,246 $2,885
23,740
kWh
- - $16,254
-
Tgal
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $13,102 $180 $13,102
109,320
kWh
- - -
03 2.1311: Replace electrically-operated equipment with fossil fuel equipment $8,142 $25,365 $10,365
85,287
kWh
$(-2,223.0)
-
MMBtu
- -
04 2.1331: Burn a less expensive grade of fuel $9,629 $17,304 $11,292
92,907
kWh
- $(-1,663.0)
-
MMBtu
-
05 2.6232: Install set-back timers $3,309 $254 $3,309
31,067
kWh
- - -
06 2.7135: Install occupancy sensors $1,995 $1,466 $1,995
16,413
kWh
- - -
07 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary $5,628 $6,425 $5,628
46,307
kWh
- - -
TOTAL RECOMMENDED $60,944 $59,240 $48,576
405,041
kWh
$(-2,223.0)
-
MMBtu
$(-1,663.0)
-
MMBtu
$16,254
-
Tgal
TOTAL IMPLEMENTED $33,663 $25,629 $35,326
296,014
kWh
- $(-1,663.0)
-
MMBtu
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings Fuel Oil #2 Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs