| Assessment Year | 1994 |
|---|---|
| Principal Product | bearing balls and frictionless bearings |
| NAICS |
n/a
|
| SIC | 3562: Ball and Roller Bearings |
| Sales Range | $10 M to 50M |
| # of Employees | 169 |
| Plant Area |
124,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 6,656
hrs
|
| Location (State) | Connecticut |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $388,977 | 4,545,721 |
kWh
|
$0.086 |
| Natural Gas | $77,698 | 9,994 |
MMBtu
|
$7.77 |
| LPG | $2,976 | 143 |
MMBtu
|
$20.81 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $77,134 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $30,282 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $14,165 | - |
$14,165
167,644
kWh
|
- | - | |
| 02 | 2.8113: Purchase gas directly from a contract gas supplier | $31,402 | $46,488 | - | - | $31,402 | |
| 03 | 2.7135: Install occupancy sensors | $9,355 | $2,620 |
$9,355
109,320
kWh
|
- | - | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,944 | - |
$5,944
69,461
kWh
|
- | - | |
| 05 | 2.2222: Convert liquid heaters from underfiring to immersion or submersion heating | $3,590 | $2,454 | - |
$3,590
-
MMBtu
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,765 | $3,077 |
$2,765
32,239
kWh
|
- | - | |
| 07 | 2.7124: Make a practice of turning off lights when not needed | $1,580 | $474 |
$1,580
18,464
kWh
|
- | - | |
| 08 | 2.2511: Insulate bare equipment | $373 | $1,024 | - |
$373
-
MMBtu
|
- | |
| 09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,095 | $12,313 |
$6,095
71,219
kWh
|
- | - | |
| 10 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $779 | $783 |
$1,129
13,189
kWh
|
$(-350.0)
-
MMBtu
|
- | |
| 11 | 2.7122: Disconnect ballasts | $677 | - |
$677
7,913
kWh
|
- | - | |
| 12 | 2.4131: Size electric motors for peak operating efficiency | $409 | $988 |
$409
4,689
kWh
|
- | - | |
| TOTAL RECOMMENDED | $77,134 | $70,221 |
$42,119
494,138
kWh
|
$3,613
-
MMBtu
|
$31,402 | ||
| TOTAL IMPLEMENTED | $30,282 | $8,800 |
$26,669
313,599
kWh
|
$3,613
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs