Assessment Year | 1989 |
---|---|
Principal Product | FLUID MILK PRODUCTS |
NAICS |
n/a
|
SIC | 2026: Fluid Milk |
Sales Range | $10 M to 50M |
# of Employees | 250 |
Plant Area |
n/a
|
Annual Production | 20,000
Tgal
|
Production Hrs. Annual | 7,344
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $331,966 | 5,096,131 |
kWh
|
$0.065 |
Natural Gas | $54,082 | 15,516 |
MMBtu
|
$3.49 |
Fuel Oil #2 | $13,604 | 2,881 |
MMBtu
|
$4.72 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,187 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,703 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #2 Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $632 | $217 |
$632
9,672
kWh
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $878 | $163 |
$878
13,482
kWh
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,825 | $500 |
$2,209
33,998
kWh
|
- | - | $1,616 | |
04 | 2.3416: Use combined cycle gas turbine generator sets with waste heat boilers connected to turbine exhaust | $19,722 | $115,000 |
$36,262
550,703
kWh
|
$(-7,360.0)
-
MMBtu
|
- | $(-9,180.0) | |
05 | 2.3191: Use demand controller or load shedder | $3,985 | $1,910 |
$3,985
-
kWh
|
- | - | - | |
06 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $530 | $218 | - |
$423
-
MMBtu
|
$107
-
MMBtu
|
- | |
07 | 2.7226: Use computer programs to optimize hvac performance | $2,615 | $3,000 |
$2,615
40,152
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $32,187 | $121,008 |
$46,581
648,007
kWh
|
$(-6,937.0)
-
MMBtu
|
$107
-
MMBtu
|
$(-7,564.0) | ||
TOTAL IMPLEMENTED | $4,703 | $663 |
$3,087
47,480
kWh
|
- | - | $1,616 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #2 Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs