| Assessment Year | 1986 |
|---|---|
| Principal Product | COATED POLYESTER FILMS |
| NAICS |
n/a
|
| SIC | 3861: Photographic Equipment and Supplies |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
n/a
|
| Annual Production | 180,000
thousand feet
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Rhode Island |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $381,482 | 5,752,931 |
kWh
|
$0.066 |
| Natural Gas | $423,515 | 69,315 |
MMBtu
|
$6.11 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $41,430 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $34,911 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $478 | $350 |
$478
7,327
kWh
|
- | |
| 02 | 2.2113: Repair or replace steam traps | $4,572 | $600 | - |
$4,572
-
MMBtu
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,763 | $4,700 |
$8,763
132,181
kWh
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,519 | $13,000 |
$6,519
98,476
kWh
|
- | |
| 05 | 2.2515: Use optimum thickness insulation | $21,098 | $5,000 | - |
$21,098
-
MMBtu
|
|
| TOTAL RECOMMENDED | $41,430 | $23,650 |
$15,760
237,984
kWh
|
$25,670
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $34,911 | $10,650 |
$9,241
139,508
kWh
|
$25,670
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs