Assessment Year | 2025 |
---|---|
Principal Product | Food & Seasonings |
NAICS | 311942: Spice and Extract Manufacturing |
SIC | 2099: Food Preparations, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 130 |
Plant Area |
180,000
ft2
|
Annual Production | 78,320,929
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,069,687 | 18,817,115 |
kWh
|
$0.057 | |
Electricity Demand | $763,292 | 44,303 |
kW-mo/yr
|
$17.23 | |
Electricity Fees | $110,987 | - |
|
- | |
Natural Gas | $372,682 | 66,082 |
MMBtu
|
$5.64 | |
Waste Disposal Costs | |||||
Water Usage | $236,929 | 51,172 |
Tgal
|
$4.63 | |
Water Disposal | $277,856 | 51,172 |
Tgal
|
$5.43 | |
TOTAL YEARLY COSTS | $2,831,433 | ||||
RECOMMENDED SAVINGS* | $648,400 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.1241: Reduce excessive boiler blowdown | $18,064 | $6,000 | - | - | - |
$10,944
-
MMBtu
|
$3,275
-
Tgal
|
$3,845
-
Tgal
|
|
02 | 2.2121: Increase amount of condensate returned | $192,452 | $260,000 | - | - | - |
$81,534
-
MMBtu
|
$51,022
-
Tgal
|
$59,896
-
Tgal
|
|
03 | 2.2621: Modify refrigeration system to operate at a lower pressure | $48,711 | $140,984 |
$48,711
857,585
kWh
|
- | - | - | - | - | |
04 | 2.3212: Optimize plant power factor | $2,409 | $19,947 | - | - | $2,409 | - | - | - | |
05 | 2.4133: Use most efficient type of electric motors | $40,176 | $29,500 |
$29,240
514,793
kWh
|
$10,935
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $56,354 | $50,550 |
$56,354
992,150
kWh
|
- | - | - | - | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,778 | - |
$2,778
48,910
kWh
|
- | - | - | - | - | |
08 | 2.7134: Use photocell controls | $417 | $340 |
$417
7,337
kWh
|
- | - | - | - | - | |
09 | 2.9114: Use solar heat to make electricty | $150,032 | $2,112,000 |
$150,032
2,641,401
kWh
|
- | - | - | - | - | |
10 | 3.4155: Meter waste water | $137,009 | $13,815 | - | - | - | - | - |
$137,009
-
Tgal
|
|
TOTAL RECOMMENDED | $648,400 | $2,633,137 |
$287,531
5,062,175
kWh
|
$10,935
-
kW-mo/yr
|
$2,409 |
$92,478
-
MMBtu
|
$54,297
-
Tgal
|
$200,749
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs