| Assessment Year | 2023 |
|---|---|
| Principal Product | Potable Water |
| NAICS | 221310: Water Supply and Irrigation Systems |
| SIC | 4941: Water Supply |
| Sales Range | $5 M to 10M |
| # of Employees | 13 |
| Plant Area |
45,743
ft2
|
| Annual Production | 1,400,000
Tgal
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $64,646 | 2,511,364 |
kWh
|
$0.026 |
| Electricity Demand | $71,124 | 4,201 |
kW-mo/yr
|
$16.93 |
| Electricity Fees | $67,123 | - |
|
- |
| Natural Gas | $28,467 | 3,943 |
MMBtu
|
$7.22 |
| TOTAL YEARLY COSTS | $231,360 | |||
| RECOMMENDED SAVINGS* | $73,336 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $24,257 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2691: Shut off cooling if cold outside air will cool process | $233 | $359 |
$233
8,943
kWh
|
- | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $73 | $316 |
$73
2,795
kWh
|
- | |
| 03 | 2.3137: Use power during off-peak periods | $24,024 | - | - |
$24,024
-
kW-mo/yr
|
|
| 04 | 2.9114: Use solar heat to make electricty | $49,006 | $1,358,975 |
$37,296
1,434,478
kWh
|
$11,710
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $73,336 | $1,359,650 |
$37,602
1,446,216
kWh
|
$35,734
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $24,257 | $359 |
$233
8,943
kWh
|
$24,024
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs