Assessment Year | 2023 |
---|---|
Principal Product | Nursing Home |
NAICS | 623110: Nursing Care Facilities (Skilled Nursing Facilities) |
SIC | 8059: Nursing and Personal Care Facilities, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 87 |
Plant Area |
68,495
ft2
|
Annual Production | 1
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $147,982 | 1,830,727 |
kWh
|
$0.081 |
Electricity Demand | $71,633 | 4,824 |
kW-mo/yr
|
$14.85 |
Electricity Fees | $10,316 | - |
|
- |
TOTAL YEARLY COSTS | $229,931 | |||
RECOMMENDED SAVINGS* | $74,539 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,663 | $39,769 |
$14,869
184,027
kWh
|
$5,793
-
kW-mo/yr
|
|
02 | 2.7134: Use photocell controls | $1,150 | $917 |
$717
8,870
kWh
|
$433
-
kW-mo/yr
|
|
03 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $4,486 | - |
$3,584
44,361
kWh
|
$902
-
kW-mo/yr
|
|
04 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $43,128 | $221,785 |
$34,453
426,400
kWh
|
$8,675
-
kW-mo/yr
|
|
05 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $5,113 | $47,950 |
$4,084
50,550
kWh
|
$1,028
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $74,539 | $310,421 |
$57,708
714,208
kWh
|
$16,831
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs