| Assessment Year | 1984 |
|---|---|
| Principal Product | COTTONSEED OIL |
| NAICS |
n/a
|
| SIC | 2074: Cottonseed Oil Mills |
| Sales Range | $10 M to 50M |
| # of Employees | 60 |
| Plant Area |
n/a
|
| Annual Production | 12,500
ton
|
| Production Hrs. Annual | 5,880
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $565,195 | 12,364,889 |
kWh
|
$0.046 |
| Natural Gas | $363,007 | 75,059 |
MMBtu
|
$4.84 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $53,480 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $47,644 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.1231: Establish burner maintenance schedule for boilers | $40,885 | $3,000 | - |
$40,885
-
MMBtu
|
|
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,836 | $2,817 |
$5,836
135,404
kWh
|
- | |
| 03 | 2.2136: Install / repair insulation on steam lines | $1,399 | $445 | - |
$1,399
-
MMBtu
|
|
| 04 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $5,360 | $9,500 | - |
$5,360
-
MMBtu
|
|
| TOTAL RECOMMENDED | $53,480 | $15,762 |
$5,836
135,404
kWh
|
$47,644
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $47,644 | $12,945 | - |
$47,644
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs