Assessment Year | 1984 |
---|---|
Principal Product | ALUMINUM CASTINGS |
NAICS |
n/a
|
SIC | 3363: Aluminum Die-Castings |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
n/a
|
Annual Production | 17,500,000
lb
|
Production Hrs. Annual | 0
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $102,969 | 2,097,597 |
kWh
|
$0.049 |
Natural Gas | $380,583 | 79,542 |
MMBtu
|
$4.78 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $98,984 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $87,314 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $6,220 | $12,200 |
$6,220
140,973
kWh
|
- | |
02 | 2.6122: Adjust vents to minimize energy use | $10,250 | $900 | - |
$10,250
-
MMBtu
|
|
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $14,340 | - | - |
$14,340
-
MMBtu
|
|
04 | 2.8114: Change rate schedules or other changes in utility service | $1,420 | - |
$1,420
-
kWh
|
- | |
05 | 2.2414: Use waste heat from hot flue gases to preheat | $66,754 | - |
$(-1,600.0)
(-35,170)
kWh
|
$68,354
-
MMBtu
|
|
TOTAL RECOMMENDED | $98,984 | $13,100 |
$6,040
105,803
kWh
|
$92,944
-
MMBtu
|
||
TOTAL IMPLEMENTED | $87,314 | $12,200 |
$4,620
105,803
kWh
|
$82,694
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs