| Assessment Year | 2023 |
|---|---|
| Principal Product | Wastewater Treatment |
| NAICS | 221320: Sewage Treatment Facilities |
| SIC | 4952: Sewerage Systems |
| Sales Range | less than $500 k |
| # of Employees | 40 |
| Plant Area |
720,000
ft2
|
| Annual Production | 3,660,000
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,349,525 | 19,371,200 |
kWh
|
$0.070 |
| Electricity Demand | $424,386 | 41,728 |
kW-mo/yr
|
$10.17 |
| Natural Gas | $239,485 | 32,626 |
MMBtu
|
$7.34 |
| TOTAL YEARLY COSTS | $2,013,396 | |||
| RECOMMENDED SAVINGS* | $151,510 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $18,486 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $133,024 | $41,910 |
$133,024
1,900,339
kWh
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,461 | $3,167 |
$3,373
48,180
kWh
|
$1,088
-
kW-mo/yr
|
|
| 03 | 2.7135: Install occupancy sensors | $158 | $125 |
$158
2,264
kWh
|
- | |
| 04 | 2.4133: Use most efficient type of electric motors | $13,867 | $56,400 |
$13,867
198,108
kWh
|
- | |
| TOTAL RECOMMENDED | $151,510 | $101,602 |
$150,422
2,148,891
kWh
|
$1,088
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $18,486 | $59,692 |
$17,398
248,552
kWh
|
$1,088
-
kW-mo/yr
|
||