Assessment Year | 2023 |
---|---|
Principal Product | Wastewater |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | less than $500 k |
# of Employees | 6 |
Plant Area |
590,764
ft2
|
Annual Production | 2,200,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $247,796 | 3,690,811 |
kWh
|
$0.067 |
Electricity Demand | $100,061 | 9,298 |
kW-mo/yr
|
$10.76 |
TOTAL YEARLY COSTS | $347,857 | |||
RECOMMENDED SAVINGS* | $39,187 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $37,613 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,574 | $150 |
$1,574
23,496
kWh
|
- | |
02 | 2.7135: Install occupancy sensors | $1,420 | $200 |
$1,420
21,193
kWh
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,702 | $4,916 |
$5,045
75,300
kWh
|
$1,657
-
kW-mo/yr
|
|
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $29,491 | $99,000 |
$29,491
440,165
kWh
|
- | |
TOTAL RECOMMENDED | $39,187 | $104,266 |
$37,530
560,154
kWh
|
$1,657
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $37,613 | $104,116 |
$35,956
536,658
kWh
|
$1,657
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs