Assessment Year | 2022 |
---|---|
Principal Product | Raw Sugar |
NAICS | 311314: Cane Sugar Manufacturing |
SIC | 2061: Cane Sugar, Except Refining |
Sales Range | less than $500 k |
# of Employees | 140 |
Plant Area |
2,381,000
ft2
|
Annual Production | 300,000,000
lb
|
Production Hrs. Annual | 5,196
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $641,720 | 5,531,735 |
kWh
|
$0.12 |
Electricity Demand | $90,477 | 22,973 |
kW-mo/yr
|
$3.94 |
TOTAL YEARLY COSTS | $732,197 | |||
RECOMMENDED SAVINGS* | $24,089 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,941 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,020 | $75 |
$6,020
51,896
kWh
|
- | |
02 | 2.7261: Install timers and/or thermostats | $4,994 | $375 |
$4,994
43,048
kWh
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,639 | $675 |
$7,639
65,846
kWh
|
- | |
04 | 2.7124: Make a practice of turning off lights when not needed | $992 | $300 |
$992
8,552
kWh
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,310 | $2,140 |
$2,112
18,209
kWh
|
$198
-
kW-mo/yr
|
|
06 | 2.7134: Use photocell controls | $2,134 | $2,590 |
$2,134
18,396
kWh
|
- | |
TOTAL RECOMMENDED | $24,089 | $6,155 |
$23,891
205,947
kWh
|
$198
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $10,941 | $3,115 |
$10,743
92,607
kWh
|
$198
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs