| Assessment Year | 2022 |
|---|---|
| Principal Product | Elementary School |
| NAICS | 611110: Elementary and Secondary Schools |
| SIC | 8211: Elementary and Secondary Schools |
| Sales Range | less than $500 k |
| # of Employees | 75 |
| Plant Area |
114,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 2,600
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $66,483 | 697,336 |
kWh
|
$0.095 |
| Electricity Demand | $10,856 | 2,643 |
kW-mo/yr
|
$4.11 |
| TOTAL YEARLY COSTS | $77,339 | |||
| RECOMMENDED SAVINGS* | $20,029 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,171 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7135: Install occupancy sensors | $590 | $200 |
$590
6,215
kWh
|
- | |
| 02 | 2.7423: Reduce heat gain by window tinting | $7,066 | $2,925 |
$7,066
74,384
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,581 | $7,172 |
$4,706
49,540
kWh
|
$875
-
kW-mo/yr
|
|
| 04 | 2.7425: Clean or color roof to reduce solar load | $5,400 | $11,760 |
$5,400
56,842
kWh
|
- | |
| 05 | 4.662: Level one – add communication using iiot devices to existing control system to modify operations | $1,392 | $5,200 |
$1,392
14,644
kWh
|
- | |
| TOTAL RECOMMENDED | $20,029 | $27,257 |
$19,154
201,625
kWh
|
$875
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $6,171 | $7,372 |
$5,296
55,755
kWh
|
$875
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs