| Assessment Year | 2024 |
|---|---|
| Principal Product | Junior Colleges and Technical Institutes |
| NAICS | 611210: Junior Colleges |
| SIC | 8222: Junior Colleges and Technical Institutes |
| Sales Range | less than $500 k |
| # of Employees | 90 |
| Plant Area |
294,726
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 3,024
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $150,162 | 1,434,112 |
kWh
|
$0.10 |
| TOTAL YEARLY COSTS | $150,162 | |||
| RECOMMENDED SAVINGS* | $44,692 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $37,714 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7224: Reduce space conditioning during non-working hours | $2,991 | - |
$2,991
28,486
kWh
|
|
| 02 | 2.2625: Chill water to the highest temperature possible | $1,667 | $250 |
$1,667
15,876
kWh
|
|
| 03 | 2.7135: Install occupancy sensors | $5,358 | $875 |
$5,358
51,024
kWh
|
|
| 04 | 2.7423: Reduce heat gain by window tinting | $1,620 | $2,352 |
$1,620
15,428
kWh
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,495 | $10,257 |
$5,495
52,337
kWh
|
|
| 06 | 2.2622: Replace existing chiller with high efficiency model | $27,561 | $98,980 |
$27,561
262,483
kWh
|
|
| TOTAL RECOMMENDED | $44,692 | $112,714 |
$44,692
425,634
kWh
|
||
| TOTAL IMPLEMENTED | $37,714 | $109,487 |
$37,714
359,182
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs