| Assessment Year | 2026 |
|---|---|
| Principal Product | Commercial Office Space |
| NAICS | 531120: Lessors of Nonresidential Buildings (except Miniwarehouses) |
| SIC | 6512: Operators of Nonresidential Buildings |
| Sales Range | less than $500 k |
| # of Employees | 10 |
| Plant Area |
99,909
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 3,120
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $164,378 | 2,207,040 |
kWh
|
$0.074 |
| Electricity Demand | $40,681 | 4,590 |
kW-mo/yr
|
$8.86 |
| TOTAL YEARLY COSTS | $205,059 | |||
| RECOMMENDED SAVINGS* | $82,562 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7135: Install occupancy sensors | $3,546 | $6,890 |
$3,546
47,923
kWh
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $24,280 | $78,000 |
$16,622
224,640
kWh
|
$7,658
-
kW-mo/yr
|
|
| 03 | 2.2437: Recover waste heat from equipment | $875 | $5,600 |
$875
11,828
kWh
|
- | |
| 04 | 2.7423: Reduce heat gain by window tinting | $24,185 | $177,207 |
$24,185
326,821
kWh
|
- | |
| 05 | 2.2622: Replace existing chiller with high efficiency model | $29,676 | $360,000 |
$20,317
274,560
kWh
|
$9,359
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $82,562 | $627,697 |
$65,545
885,772
kWh
|
$17,017
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||