Assessment Year 2022
Principal Product Refrigerated Warehousing and Storage
NAICS 493120: Refrigerated Warehousing and Storage
SIC 4222: Refrigerated Warehousing and Storage
Sales Range less than $500
k
# of Employees 20
Plant Area 150,000
ft2
Annual Production 1
units
Production Hrs. Annual 8,760
hrs
Location (State) Louisiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $140,540 1,758,000
kWh
Electricity Demand $27,604 5,474
kW-mo/yr
TOTAL YEARLY COSTS $168,144
RECOMMENDED SAVINGS* $106,838 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $92,305

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings
01 2.7135: Install occupancy sensors $17,059 $500 $17,059
213,394
kWh
- -
02 2.7134: Use photocell controls $9,454 $999 $9,454
118,260
kWh
- -
03 2.7447: Install vinyl strip / high speed / air curtain doors $1,264 $240 $1,264
15,809
kWh
- -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $74,562 $14,625 $68,031
850,994
kWh
$6,531
-
kW-mo/yr
-
05 2.7444: Close holes and openings in building such as broken windows $684 $660 $684
8,550
kWh
- -
06 4.463: Modify facility to avoid excess maintenance costs $3,815 $17,858 - - $3,815
TOTAL RECOMMENDED $106,838 $34,882 $96,492
1,207,007
kWh
$6,531
-
kW-mo/yr
$3,815
TOTAL IMPLEMENTED $92,305 $15,785 $85,774
1,072,938
kWh
$6,531
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs