| Assessment Year | 2026 |
|---|---|
| Principal Product | Business Associations |
| NAICS | 813910: Business Associations |
| SIC | 8611: Business Associations |
| Sales Range | less than $500 k |
| # of Employees | 20 |
| Plant Area |
26,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 4,850
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $60,484 | 645,800 |
kWh
|
$0.094 |
| Electricity Demand | $15,985 | 1,798 |
kW-mo/yr
|
$8.89 |
| Natural Gas | $4,930 | 795 |
MMBtu
|
$6.20 |
| TOTAL YEARLY COSTS | $81,399 | |||
| RECOMMENDED SAVINGS* | $123,501 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7226: Use computer programs to optimize hvac performance | $1,516 | $50 |
$1,516
16,134
kWh
|
- | |
| 02 | 2.7135: Install occupancy sensors | $4,431 | $2,000 |
$4,431
47,140
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,324 | $10,536 |
$8,369
89,032
kWh
|
$1,955
-
kW-mo/yr
|
|
| 04 | 2.2622: Replace existing chiller with high efficiency model | $107,230 | $700,000 |
$107,230
1,140,750
kWh
|
- | |
| TOTAL RECOMMENDED | $123,501 | $712,586 |
$121,546
1,293,056
kWh
|
$1,955
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs