Assessment Year | 2022 |
---|---|
Principal Product | Retails |
NAICS | 451110: Sporting Goods Stores |
SIC | 5941: Sporting Goods Stores and Bicycle Shops |
Sales Range | less than $500 k |
# of Employees | 130 |
Plant Area |
166,594
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 5,460
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $273,666 | 3,808,000 |
kWh
|
$0.072 |
Electricity Demand | $34,431 | 8,357 |
kW-mo/yr
|
$4.12 |
TOTAL YEARLY COSTS | $308,097 | |||
RECOMMENDED SAVINGS* | $65,348 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $65,348 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7211: Clean and maintain refrigerant condensers and towers | $13,696 | - |
$13,696
190,217
kWh
|
- | |
02 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $942 | $300 |
$942
13,104
kWh
|
- | |
03 | 2.7135: Install occupancy sensors | $1,436 | $575 |
$1,436
19,988
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $46,495 | $39,219 |
$41,242
572,803
kWh
|
$5,253
-
kW-mo/yr
|
|
05 | 2.2515: Use optimum thickness insulation | $2,779 | $6,297 |
$2,779
38,671
kWh
|
- | |
TOTAL RECOMMENDED | $65,348 | $46,391 |
$60,095
834,783
kWh
|
$5,253
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $65,348 | $46,391 |
$60,095
834,783
kWh
|
$5,253
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs