Assessment Year | 2017 |
---|---|
Principal Product | Museum |
NAICS | 712110: Museums |
SIC | 8422: Arboreta and Botanical or Zoological Gardens |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
168,104
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $535,774 | 8,401,519 |
kWh
|
$0.064 | |
Electricity Demand | $115,830 | 14,961 |
kW-mo/yr
|
$7.74 | |
Natural Gas | $27,272 | 4,111 |
MMBtu
|
$6.63 | |
Waste Disposal Costs | |||||
Water Usage | $102,731 | 20,134 |
Tgal
|
$5.10 | |
TOTAL YEARLY COSTS | $781,607 | ||||
RECOMMENDED SAVINGS* | $36,431 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.7273: Install desiccant humidity control system | $17,595 | - |
$15,094
235,840
kWh
|
$2,501
-
kW-mo/yr
|
- | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $1,307 | - |
$1,121
17,520
kWh
|
$186
-
kW-mo/yr
|
- | |
03 | 2.7124: Make a practice of turning off lights when not needed | $1,869 | - |
$1,869
29,200
kWh
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,982 | - |
$1,700
26,561
kWh
|
$282
-
kW-mo/yr
|
- | |
05 | 2.2511: Insulate bare equipment | $12,478 | - |
$10,705
167,265
kWh
|
$1,773
-
kW-mo/yr
|
- | |
06 | 4.463: Modify facility to avoid excess maintenance costs | $1,200 | - | - | - | $1,200 | |
TOTAL RECOMMENDED | $36,431 | - |
$30,489
476,386
kWh
|
$4,742
-
kW-mo/yr
|
$1,200 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs