Assessment Year | 2004 |
---|---|
Principal Product | electroplated parts |
NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
Sales Range | $1 M to 5M |
# of Employees | 123 |
Plant Area |
40,000
ft2
|
Annual Production | 6,000,000
pieces
|
Production Hrs. Annual | 3,500
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $67,069 | 627,932 |
kWh
|
$0.11 |
Electricity Demand | $20,003 | 2,484 |
kW-mo/yr
|
$8.05 |
Electricity Fees | $(-1,688.0) | - |
|
- |
Natural Gas | $61,112 | 7,573 |
MMBtu
|
$8.07 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $534,828 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,857 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,802 | - |
$1,434
12,708
kWh
|
$368
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.4239: Eliminate or reduce compressed air usage | $2,857 | $300 |
$2,273
20,142
kWh
|
$584
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.4131: Size electric motors for peak operating efficiency | $85 | - |
$62
545
kWh
|
$16
-
kW-mo/yr
|
$7 | - | - | - | |
04 | 2.4133: Use most efficient type of electric motors | $160 | $80 |
$127
1,122
kWh
|
$33
-
kW-mo/yr
|
- | - | - | - | |
05 | 4.121: Maintain clean conditions before painting | $233,065 | $1,000 |
$3,632
32,179
kWh
|
- | - |
$4,561
-
MMBtu
|
$(-19,562.0) | $244,434 | |
06 | 4.121: Maintain clean conditions before painting | $292,248 | $4,925 |
$4,146
36,734
kWh
|
- | - |
$3,557
-
MMBtu
|
- | $284,545 | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $4,611 | $1,814 |
$3,782
31,159
kWh
|
$829
-
kW-mo/yr
|
- | - | - | - | |
TOTAL RECOMMENDED | $534,828 | $8,119 |
$15,456
134,589
kWh
|
$1,830
-
kW-mo/yr
|
$7 |
$8,118
-
MMBtu
|
$(-19,562.0) | $528,979 | ||
TOTAL IMPLEMENTED | $2,857 | $300 |
$2,273
20,142
kWh
|
$584
-
kW-mo/yr
|
- | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs