Assessment Year 2004
Principal Product Steel Bed Frames and Parts
NAICS 337124: Metal Household Furniture Manufacturing
SIC 2514: Metal Household Furniture
Sales Range $50
M
to 100
M
# of Employees 255
Plant Area 175,000
ft2
Annual Production 7,322,544
lb
Production Hrs. Annual 4,000
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $268,610 2,332,899
kWh
Electricity Demand $102,261 8,328
kW-mo/yr
Electricity Fees $20,301 -
Natural Gas $162,622 21,530
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $318,390 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $52,605

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Administrative Changes Savings Primary Product Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,682 $1,300 $2,869
24,188
kWh
$813
-
kW-mo/yr
- - - -
02 2.4239: Eliminate or reduce compressed air usage $8,649 - $6,513
54,960
kWh
$2,136
-
kW-mo/yr
- - - -
03 2.4231: Reduce the pressure of compressed air to the minimum required $5,384 - $4,199
35,424
kWh
$1,185
-
kW-mo/yr
- - - -
04 2.7131: Add area lighting switches $6,155 $1,600 $4,690
39,571
kWh
$1,465
-
kW-mo/yr
- - - -
05 2.7144: Install spectral reflectors / delamp $784 - $597
5,040
kWh
$187
-
kW-mo/yr
- - - -
06 2.4133: Use most efficient type of electric motors $1,570 $1,093 $1,182
9,974
kWh
$388
-
kW-mo/yr
- - - -
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $3,911 $3,520 $2,951
24,895
kWh
$960
-
kW-mo/yr
- - - -
08 2.2414: Use waste heat from hot flue gases to preheat $9,302 $10,000 - - $9,302
-
MMBtu
- - -
09 4.321: Optimize production lot sizes and inventories $27,520 $4,000 - - - - - $27,520
10 4.522: Modify storage space to avoid rental of a warehouse $207,176 - - - - - $207,176 -
11 4.431: Train operators for maximum operating efficiency $10,400 $1,562 - - - $10,400 - -
12 4.625: Develop standard operating procedures $33,857 $9,860 - - - $33,857 - -
TOTAL RECOMMENDED $318,390 $32,935 $23,001
194,052
kWh
$7,134
-
kW-mo/yr
$9,302
-
MMBtu
$44,257 $207,176 $27,520
TOTAL IMPLEMENTED $52,605 $7,955 $11,161
94,162
kWh
$3,524
-
kW-mo/yr
- $10,400 - $27,520
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Administrative Changes Savings Primary Product Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs