Assessment Year 2004
Principal Product Plastic and Metal Fixtures
NAICS 326199: All Other Plastics Product Manufacturing
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $5
M
to 10
M
# of Employees 50
Plant Area 87,000
ft2
Annual Production 2,500,000
pieces
Production Hrs. Annual 4,000
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $198,632 1,576,092
kWh
Electricity Demand $45,854 4,740
kW-mo/yr
Electricity Fees $25,302 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $22,807 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $5,094

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Consumption Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $1,620 - $1,344
11,963
kWh
$276
-
kW-mo/yr
-
02 2.6218: Turn off equipment when not in use $110 - $88
872
kWh
$22
-
kW-mo/yr
-
03 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $17,713 $17,500 $14,439
128,561
kWh
$3,274
-
kW-mo/yr
-
04 2.2611: Moderate cooling tower outlet temperature $2,061 - $2,061
18,348
kWh
- -
05 2.2511: Insulate bare equipment $102 $96 $102
905
kWh
- -
06 3.5315: Lease / purchase baler; sell cardboard to recycler $1,201 - - - $1,201
-
Tgal
TOTAL RECOMMENDED $22,807 $17,596 $18,034
160,649
kWh
$3,572
-
kW-mo/yr
$1,201
-
Tgal
TOTAL IMPLEMENTED $5,094 $96 $3,595
32,088
kWh
$298
-
kW-mo/yr
$1,201
-
Tgal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs