Assessment Year 2012
Principal Product Ships
NAICS 336612: Boat Building
SIC 3732: Boat Building and Repairing
Sales Range $100
M
to 500
M
# of Employees 700
Plant Area 300,000
ft2
Annual Production 4
pieces
Production Hrs. Annual 4,680
hrs
Location (State) Louisiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $797,144 10,829,000
kWh
Electricity Demand $4,118 7,487
kW-mo/yr
Electricity Fees $4,180 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $308,313 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings Administrative Changes Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $157,413 $35,600 $157,247
2,136,215
kWh
$166
-
kW-mo/yr
- -
02 2.7111: Reduce illumination to minimum necessary levels $110,468 $2,180 $109,061
1,481,607
kWh
$1,407
-
kW-mo/yr
- -
03 4.611: Begin a practice of predictive / preventative maintenance $17,664 $6,849 - - $17,664 -
04 2.7229: Air condition only space necessary $15,433 $30 $15,433
209,664
kWh
- - -
05 2.7135: Install occupancy sensors $1,648 $5,820 $1,648
22,384
kWh
- - -
06 4.611: Begin a practice of predictive / preventative maintenance $1,986 $1,500 $486
6,601
kWh
- - $1,500
07 2.7224: Reduce space conditioning during non-working hours $1,061 $1,089 $1,061
14,416
kWh
- - -
08 2.6211: Conserve energy by efficient use of vending machines $940 $1,654 $940
12,776
kWh
- - -
09 2.7142: Utilize higher efficiency lamps and/or ballasts $932 $4,620 $902
12,252
kWh
$30
-
kW-mo/yr
- -
10 2.7142: Utilize higher efficiency lamps and/or ballasts $769 $418 $769
10,442
kWh
- - -
TOTAL RECOMMENDED $308,313 $59,760 $287,547
3,906,357
kWh
$1,602
-
kW-mo/yr
$17,664 $1,500
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs