Assessment Year 2011
Principal Product Ships
NAICS 336611: Ship Building and Repairing
SIC 3731: Ship Building and Repairing
Sales Range $100
M
to 500
M
# of Employees 518
Plant Area 384,000
ft2
Annual Production 4
pieces
Production Hrs. Annual 5,200
hrs
Location (State) Louisiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $212,773 2,828,066
kWh
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $116,873 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $72,556

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings One-time Revenue or Avoided Cost Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $72,556 $22,440 $72,556
964,323
kWh
-
02 2.4231: Reduce the pressure of compressed air to the minimum required $23,693 $30 $23,693
314,900
kWh
-
03 2.7224: Reduce space conditioning during non-working hours $15,381 $990 $15,381
204,422
kWh
-
04 4.611: Begin a practice of predictive / preventative maintenance $3,312 $1,200 $1,812
24,080
kWh
$1,500
05 2.6211: Conserve energy by efficient use of vending machines $1,052 $1,470 $1,052
13,978
kWh
-
06 2.7135: Install occupancy sensors $594 $2,275 $594
7,891
kWh
-
07 2.6211: Conserve energy by efficient use of vending machines $270 $88 $270
3,591
kWh
-
08 2.7134: Use photocell controls $15 $90 $15
200
kWh
-
TOTAL RECOMMENDED $116,873 $28,583 $115,373
1,533,385
kWh
$1,500
TOTAL IMPLEMENTED $72,556 $22,440 $72,556
964,323
kWh
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs