ITAC Assessment: LL0339
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2010
Principal Product Wood products
NAICS 321912: Cut Stock, Resawing Lumber, and Planing
SIC 2421: Sawmills and Planing Mills, General
Sales Range $10
M
to 50
M
# of Employees 105
Plant Area 450,000
ft2
Annual Production 93,000,000
pieces
Production Hrs. Annual 8,736
hrs
Location (State) Arkansas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $4,519,176 71,646,400
kWh
Electricity Fees $162,269 -
Natural Gas $4,856,640 701,760
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $676,480 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $628,698

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Fees Savings Natural Gas Savings
01 2.2135: Repair and eliminate steam leaks $271,505 $2,920 - - $271,505
-
MMBtu
02 2.2121: Increase amount of condensate returned $204,298 $966,460 - - $204,298
-
MMBtu
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $152,895 $42,400 $147,595
2,339,807
kWh
$5,300 -
04 2.2511: Insulate bare equipment $31,760 $6,240 - - $31,760
-
MMBtu
05 2.7111: Reduce illumination to minimum necessary levels $5,510 $10,605 $5,319
84,315
kWh
$191 -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $5,365 $1,950 $5,179
82,105
kWh
$186 -
07 2.7135: Install occupancy sensors $3,388 $1,950 $3,271
51,854
kWh
$117 -
08 2.7134: Use photocell controls $1,302 $150 $1,257
19,921
kWh
$45 -
09 2.6211: Conserve energy by efficient use of vending machines $457 $623 $441
6,989
kWh
$16 -
TOTAL RECOMMENDED $676,480 $1,033,298 $163,062
2,584,991
kWh
$5,855 $507,563
-
MMBtu
TOTAL IMPLEMENTED $628,698 $1,011,780 $147,595
2,339,807
kWh
$5,300 $475,803
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Fees Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs