Assessment Year | 2008 |
---|---|
Principal Product | Paper Sausage Casings |
NAICS | 311611: Animal (except Poultry) Slaughtering |
SIC | 2013: Sausages and Other Prepared Meat Products |
Sales Range | $100 M to 500M |
# of Employees | 300 |
Plant Area |
252,000
ft2
|
Annual Production | 2,300,000
thousand feet
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,474,643 | 27,214,664 |
kWh
|
$0.054 |
Natural Gas | $3,311,726 | 345,682 |
MMBtu
|
$9.58 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $338,592 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $336,410 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $230,177 | $13,140 | - |
$230,177
-
MMBtu
|
- | |
02 | 2.2511: Insulate bare equipment | $86,230 | $9,006 | - |
$86,230
-
MMBtu
|
- | |
03 | 2.2511: Insulate bare equipment | $11,367 | $11,696 |
$11,367
212,868
kWh
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,117 | $2,720 |
$7,117
133,279
kWh
|
- | - | |
05 | 2.7224: Reduce space conditioning during non-working hours | $1,436 | $1,650 |
$1,436
26,883
kWh
|
- | - | |
06 | 2.6211: Conserve energy by efficient use of vending machines | $746 | $1,246 |
$746
13,970
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,156 | $840 |
$427
7,989
kWh
|
- | $729 | |
08 | 2.7134: Use photocell controls | $363 | $150 |
$363
6,796
kWh
|
- | - | |
TOTAL RECOMMENDED | $338,592 | $40,448 |
$21,456
401,785
kWh
|
$316,407
-
MMBtu
|
$729 | ||
TOTAL IMPLEMENTED | $336,410 | $37,552 |
$19,274
360,932
kWh
|
$316,407
-
MMBtu
|
$729 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs