Assessment Year | 2007 |
---|---|
Principal Product | Flow meeters |
NAICS | 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial |
SIC | 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products |
Sales Range | $100 M to 500M |
# of Employees | 30 |
Plant Area |
14,000
ft2
|
Annual Production | 1,000
pieces
|
Production Hrs. Annual | 2,375
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $32,612 | 338,123 |
kWh
|
$0.096 |
Electricity Demand | $4,747 | 1,579 |
kW-mo/yr
|
$3.01 |
Electricity Fees | $1,233 | - |
|
- |
Natural Gas | $1,508 | 84 |
MMBtu
|
$17.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $7,332 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,032 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 4.611: Begin a practice of predictive / preventative maintenance | $3,109 | $60 |
$1,558
16,150
kWh
|
$51 | $1,500 | |
02 | 2.4238: Do not use compressed air for personal cooling | $1,914 | $1,160 |
$1,853
19,208
kWh
|
$61 | - | |
03 | 2.7135: Install occupancy sensors | $1,056 | $900 |
$1,022
10,596
kWh
|
$34 | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $603 | $252 |
$584
6,060
kWh
|
$19 | - | |
05 | 2.7224: Reduce space conditioning during non-working hours | $291 | $330 |
$282
2,923
kWh
|
$9 | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $145 | $1,734 |
$140
1,455
kWh
|
$5 | - | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $115 | $319 |
$111
1,150
kWh
|
$4 | - | |
08 | 2.2511: Insulate bare equipment | $99 | $81 |
$96
994
kWh
|
$3 | - | |
TOTAL RECOMMENDED | $7,332 | $4,836 |
$5,646
58,536
kWh
|
$186 | $1,500 | ||
TOTAL IMPLEMENTED | $6,032 | $2,121 |
$4,388
45,491
kWh
|
$144 | $1,500 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs