Assessment Year | 2006 |
---|---|
Principal Product | Carbon Black |
NAICS | 325180: Other Basic Inorganic Chemical Manufacturing |
SIC | 2895: Carbon Black |
Sales Range | $100 M to 500M |
# of Employees | 150 |
Plant Area |
250,000
ft2
|
Annual Production | 140,000
ton
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $4,228,265 | 61,844,550 |
kWh
|
$0.068 |
Electricity Demand | $753,234 | 101,939 |
kW-mo/yr
|
$7.39 |
Electricity Fees | $184,944 | - |
|
- |
Natural Gas | $19,016,134 | 2,048,426 |
MMBtu
|
$9.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $3,855,622 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $95,961 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1336: Install equipment to utilize waste fuel | $3,668,421 | $1,500,000 | - | - | - |
$3,668,421
-
MMBtu
|
- | |
02 | 2.7134: Use photocell controls | $68,323 | $3,630 |
$65,883
963,203
kWh
|
- | $2,440 | - | - | |
03 | 2.7224: Reduce space conditioning during non-working hours | $65,870 | $8,195 |
$63,517
928,612
kWh
|
- | $2,353 | - | - | |
04 | 2.7134: Use photocell controls | $27,638 | $4,050 |
$26,651
389,631
kWh
|
- | $987 | - | - | |
05 | 2.7135: Install occupancy sensors | $18,294 | $2,190 |
$17,641
257,904
kWh
|
- | $653 | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,321 | $3,850 |
$2,505
36,617
kWh
|
$370
-
kW-mo/yr
|
$106 | - | $3,340 | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $755 | $432 |
$447
6,529
kWh
|
$281
-
kW-mo/yr
|
$27 | - | - | |
TOTAL RECOMMENDED | $3,855,622 | $1,522,347 |
$176,644
2,582,496
kWh
|
$651
-
kW-mo/yr
|
$6,566 |
$3,668,421
-
MMBtu
|
$3,340 | ||
TOTAL IMPLEMENTED | $95,961 | $7,680 |
$92,534
1,352,834
kWh
|
- | $3,427 | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs