Assessment Year | 2006 |
---|---|
Principal Product | Chicken Products |
NAICS | 311615: Poultry Processing |
SIC | 2015: Poultry Slaughtering and Processing |
Sales Range | $100 M to 500M |
# of Employees | 600 |
Plant Area |
125,000
ft2
|
Annual Production | 208,000,000
lb
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,337,263 | 37,017,180 |
kWh
|
$0.063 |
Electricity Demand | $234,907 | 74,381 |
kW-mo/yr
|
$3.16 |
Electricity Fees | $126,945 | - |
|
- |
Natural Gas | $1,518,292 | 148,829 |
MMBtu
|
$10.20 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $418,953 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $398,467 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $219,845 | $2,900 | - | - | - |
$219,845
-
MMBtu
|
- | - | |
02 | 2.2121: Increase amount of condensate returned | $111,471 | $70,939 | - | - | - |
$80,019
-
MMBtu
|
- |
$31,452
-
Tgal
|
|
03 | 2.2511: Insulate bare equipment | $35,700 | $11,209 |
$34,032
539,339
kWh
|
- | $1,668 | - | - | - | |
04 | 2.2511: Insulate bare equipment | $20,392 | $3,960 | - | - | - |
$20,392
-
MMBtu
|
- | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $12,350 | $720 |
$11,018
174,614
kWh
|
$755
-
kW-mo/yr
|
$577 | - | - | - | |
06 | 3.4154: Eliminate leaks in water lines and valves | $7,057 | $1,330 | - | - | - | - | - |
$7,057
-
Tgal
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,368 | $30 |
$5,117
81,097
kWh
|
- | $251 | - | - | - | |
08 | 2.7135: Install occupancy sensors | $2,768 | $210 |
$2,639
41,829
kWh
|
- | $129 | - | - | - | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,347 | $640 |
$2,237
35,450
kWh
|
- | $110 | - | - | - | |
10 | 2.7134: Use photocell controls | $870 | $90 |
$829
13,137
kWh
|
- | $41 | - | - | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $785 | $700 |
$315
4,993
kWh
|
- | $15 | - | $455 | - | |
TOTAL RECOMMENDED | $418,953 | $92,728 |
$56,187
890,459
kWh
|
$755
-
kW-mo/yr
|
$2,791 |
$320,256
-
MMBtu
|
$455 |
$38,509
-
Tgal
|
||
TOTAL IMPLEMENTED | $398,467 | $91,768 |
$37,413
592,919
kWh
|
- | $1,834 |
$320,256
-
MMBtu
|
$455 |
$38,509
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs