Assessment Year | 2006 |
---|---|
Principal Product | Polyethylene |
NAICS | 324199: All Other Petroleum and Coal Products Manufacturing |
SIC | 2999: Products of Petroleum and Coal, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 100 |
Plant Area |
94,700
ft2
|
Annual Production | 88,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,353,975 | 25,885,934 |
kWh
|
$0.052 |
Electricity Demand | $296,512 | 44,927 |
kW-mo/yr
|
$6.60 |
Electricity Fees | $4,903 | - |
|
- |
Natural Gas | $1,814,223 | 269,571 |
MMBtu
|
$6.73 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $826,634 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $316,725 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|
01 | 2.2121: Increase amount of condensate returned | $490,346 | $849,320 | - |
$429,845
-
MMBtu
|
$60,501
-
Tgal
|
|
02 | 2.2135: Repair and eliminate steam leaks | $240,584 | $34,600 | - |
$240,584
-
MMBtu
|
- | |
03 | 2.7224: Reduce space conditioning during non-working hours | $72,332 | $3,042 |
$72,332
1,382,760
kWh
|
- | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $14,933 | $122,080 |
$14,933
285,462
kWh
|
- | - | |
05 | 2.7135: Install occupancy sensors | $3,024 | $300 |
$3,024
57,817
kWh
|
- | - | |
06 | 2.2511: Insulate bare equipment | $2,093 | $313 | - |
$2,093
-
MMBtu
|
- | |
07 | 2.2511: Insulate bare equipment | $1,716 | $913 | - |
$1,716
-
MMBtu
|
- | |
08 | 2.7134: Use photocell controls | $1,606 | $150 |
$1,606
30,704
kWh
|
- | - | |
TOTAL RECOMMENDED | $826,634 | $1,010,718 |
$91,895
1,756,743
kWh
|
$674,238
-
MMBtu
|
$60,501
-
Tgal
|
||
TOTAL IMPLEMENTED | $316,725 | $38,868 |
$72,332
1,382,760
kWh
|
$244,393
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs