| Assessment Year | 2005 |
|---|---|
| Principal Product | Rice Drying |
| NAICS | 311212: Rice Milling |
| SIC | 2044: Rice Milling |
| Sales Range | $500 k to 1M |
| # of Employees | 16 |
| Plant Area |
50,000
ft2
|
| Annual Production | 13,364,000
lb
|
| Production Hrs. Annual | 3,984
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $64,924 | 691,635 |
kWh
|
$0.094 |
| Electricity Demand | $9,940 | 1,473 |
kW-mo/yr
|
$6.75 |
| Electricity Fees | $2,850 | - |
|
- |
| Natural Gas | $43,465 | 3,515 |
MMBtu
|
$12.37 |
| Other Gas | $17,631 | 1,376 |
MMBtu
|
$12.81 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $49,016 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $22,760 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Other Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.2511: Insulate bare equipment | $24,360 | - | - | - | - |
$13,899
-
MMBtu
|
$10,461
-
MMBtu
|
- | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $9,515 | $2,800 |
$9,167
97,654
kWh
|
- | $348 | - | - | - | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,336 | $2,600 |
$5,017
53,446
kWh
|
$1,087
-
kW-mo/yr
|
$232 | - | - | - | - | |
| 04 | 2.7134: Use photocell controls | $1,045 | - |
$1,007
10,728
kWh
|
- | $38 | - | - | - | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $944 | $150 | - | - | - |
$944
-
MMBtu
|
- | - | - | |
| 06 | 2.7135: Install occupancy sensors | $851 | - |
$820
8,735
kWh
|
- | $31 | - | - | - | - | |
| 07 | 2.8114: Change rate schedules or other changes in utility service | $465 | - | - | - | $465 | - | - | - | - | |
| 08 | 4.611: Begin a practice of predictive / preventative maintenance | $5,500 | $250 | - | - | - | - | - | $1,500 | $4,000 | |
| TOTAL RECOMMENDED | $49,016 | $5,800 |
$16,011
170,563
kWh
|
$1,087
-
kW-mo/yr
|
$1,114 |
$14,843
-
MMBtu
|
$10,461
-
MMBtu
|
$1,500 | $4,000 | ||
| TOTAL IMPLEMENTED | $22,760 | $5,800 |
$14,184
151,100
kWh
|
$1,087
-
kW-mo/yr
|
$1,045 |
$944
-
MMBtu
|
- | $1,500 | $4,000 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Other Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs