Assessment Year | 2004 |
---|---|
Principal Product | ship and repair |
NAICS | 336611: Ship Building and Repairing |
SIC | 3731: Ship Building and Repairing |
Sales Range | $5 M to 10M |
# of Employees | 40 |
Plant Area |
60,000
ft2
|
Annual Production | 54
pieces
|
Production Hrs. Annual | 3,510
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $85,501 | 1,473,546 |
kWh
|
$0.058 |
Electricity Demand | $25,765 | 8,441 |
kW-mo/yr
|
$3.05 |
Electricity Fees | $3,815 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $16,461 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,428 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $4,929 | $825 |
$3,805
65,578
kWh
|
$972
-
kW-mo/yr
|
$152 | - | - | |
02 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $2,415 | $895 |
$2,336
40,256
kWh
|
- | $79 | - | - | |
03 | 2.7134: Use photocell controls | $899 | $30 |
$869
14,976
kWh
|
- | $30 | - | - | |
04 | 2.7224: Reduce space conditioning during non-working hours | $778 | $990 |
$752
12,961
kWh
|
- | $26 | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $755 | $525 |
$290
4,993
kWh
|
- | $10 | $455 | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $754 | $1,120 |
$729
12,571
kWh
|
- | $25 | - | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $261 | $30 |
$252
4,342
kWh
|
- | $9 | - | - | |
08 | 2.7134: Use photocell controls | $170 | $270 |
$164
2,830
kWh
|
- | $6 | - | - | |
09 | 4.611: Begin a practice of predictive / preventative maintenance | $5,500 | $1,050 | - | - | - | $3,000 | $2,500 | |
TOTAL RECOMMENDED | $16,461 | $5,735 |
$9,197
158,507
kWh
|
$972
-
kW-mo/yr
|
$337 | $3,455 | $2,500 | ||
TOTAL IMPLEMENTED | $9,428 | $3,170 |
$8,155
140,553
kWh
|
$972
-
kW-mo/yr
|
$301 | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs