Assessment Year | 2004 |
---|---|
Principal Product | ship and repair |
NAICS | 336611: Ship Building and Repairing |
SIC | 3731: Ship Building and Repairing |
Sales Range | $10 M to 50M |
# of Employees | 85 |
Plant Area |
85,000
ft2
|
Annual Production | 10
pieces
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $236,316 | 3,765,560 |
kWh
|
$0.063 |
Electricity Demand | $39,436 | 19,717 |
kW-mo/yr
|
$2.00 |
Electricity Fees | $7,833 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $154,359 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $138,083 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $107,401 | $19,500 |
$104,476
1,664,687
kWh
|
- | $2,925 | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,303 | $12,640 |
$12,941
206,197
kWh
|
- | $362 | - | - | |
03 | 2.7134: Use photocell controls | $8,552 | $882 |
$8,319
132,560
kWh
|
- | $233 | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,124 | $30 |
$5,957
94,924
kWh
|
- | $167 | - | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $1,679 | $489 |
$1,405
22,391
kWh
|
$228
-
kW-mo/yr
|
$46 | - | - | |
06 | 2.7135: Install occupancy sensors | $1,024 | $1,080 |
$996
15,878
kWh
|
- | $28 | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $557 | $990 |
$542
8,641
kWh
|
- | $15 | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $519 | $350 |
$209
3,329
kWh
|
- | $6 | $304 | - | |
09 | 4.611: Begin a practice of predictive / preventative maintenance | $15,200 | $2,100 | - | - | - | $10,200 | $5,000 | |
TOTAL RECOMMENDED | $154,359 | $38,061 |
$134,845
2,148,607
kWh
|
$228
-
kW-mo/yr
|
$3,782 | $10,504 | $5,000 | ||
TOTAL IMPLEMENTED | $138,083 | $34,621 |
$134,094
2,136,637
kWh
|
$228
-
kW-mo/yr
|
$3,761 | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs