Assessment Year | 2004 |
---|---|
Principal Product | Metal Tanks |
NAICS | 332420: Metal Tank (Heavy Gauge) Manufacturing |
SIC | 3443: Fabricated Plate Work (Boiler Shops) |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
65,000
ft2
|
Annual Production | 250
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $124,393 | 2,187,763 |
kWh
|
$0.057 |
Electricity Demand | $43,549 | 7,728 |
kW-mo/yr
|
$5.64 |
Electricity Fees | $9,161 | - |
|
- |
Natural Gas | $2,603 | 233 |
MMBtu
|
$11.17 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $61,699 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $44,062 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $29,094 | $4,650 |
$27,577
485,000
kWh
|
- | $1,517 | - | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $8,122 | $48 |
$7,699
135,399
kWh
|
- | $423 | - | - | |
03 | 2.7134: Use photocell controls | $7,508 | $600 |
$7,117
125,163
kWh
|
- | $391 | - | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $3,551 | $195 |
$2,875
50,563
kWh
|
$491
-
kW-mo/yr
|
$185 | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,104 | $2,080 |
$2,942
51,738
kWh
|
- | $162 | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,748 | $4,250 | - | - | - | - | $2,748 | |
07 | 2.7132: Install timers on light switches in little used areas | $1,313 | $96 |
$1,245
21,902
kWh
|
- | $68 | - | - | |
08 | 2.7135: Install occupancy sensors | $694 | $90 |
$658
11,565
kWh
|
- | $36 | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $452 | $315 |
$170
2,996
kWh
|
- | $9 | $273 | - | |
10 | 2.8112: Combine utility meters | $2,613 | $720 | - | - | $2,613 | - | - | |
11 | 4.611: Begin a practice of predictive / preventative maintenance | $2,500 | $60 | - | - | - | $2,500 | - | |
TOTAL RECOMMENDED | $61,699 | $13,104 |
$50,283
884,326
kWh
|
$491
-
kW-mo/yr
|
$5,404 | $2,773 | $2,748 | ||
TOTAL IMPLEMENTED | $44,062 | $12,270 |
$33,564
590,297
kWh
|
$491
-
kW-mo/yr
|
$4,486 | $2,773 | $2,748 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs