Assessment Year | 2004 |
---|---|
Principal Product | Control Boxes |
NAICS | 335314: Relay and Industrial Control Manufacturing |
SIC | 3625: Relays and Industrial Controls |
Sales Range | $50 M to 100M |
# of Employees | 75 |
Plant Area |
49,200
ft2
|
Annual Production | 1,000
pieces
|
Production Hrs. Annual | 3,120
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $77,828 | 1,198,488 |
kWh
|
$0.065 |
Electricity Demand | $11,875 | 3,699 |
kW-mo/yr
|
$3.21 |
Electricity Fees | $3,473 | - |
|
- |
Natural Gas | $50,968 | 7,553 |
MMBtu
|
$6.75 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $15,988 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,454 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $5,280 | $9,967 |
$5,082
78,250
kWh
|
- | $198 | - | - | |
02 | 2.8123: Pay utility bills on time | $3,954 | $30 | - | - | $3,954 | - | - | |
03 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,594 | $1,720 |
$1,534
23,626
kWh
|
- | $60 | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,196 | $770 |
$476
7,323
kWh
|
$32
-
kW-mo/yr
|
$20 | - | $668 | |
05 | 2.7135: Install occupancy sensors | $1,041 | $495 |
$1,002
15,433
kWh
|
- | $39 | - | - | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $959 | $248 |
$737
11,356
kWh
|
$186
-
kW-mo/yr
|
$36 | - | - | |
07 | 2.6212: Turn off equipment during breaks, reduce operating time | $363 | $288 |
$349
5,376
kWh
|
- | $14 | - | - | |
08 | 2.7134: Use photocell controls | $101 | $56 |
$97
1,496
kWh
|
- | $4 | - | - | |
09 | 4.611: Begin a practice of predictive / preventative maintenance | $1,500 | $60 | - | - | - | $1,500 | - | |
TOTAL RECOMMENDED | $15,988 | $13,634 |
$9,277
142,860
kWh
|
$218
-
kW-mo/yr
|
$4,325 | $1,500 | $668 | ||
TOTAL IMPLEMENTED | $5,454 | $90 | - | - | $3,954 | $1,500 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs