Assessment Year | 2003 |
---|---|
Principal Product | Oilfield service equipment |
NAICS | 333132: Oil and Gas Field Machinery and Equipment Manufacturing |
SIC | 3533: Oil and Gas Field Machinery and Equipment |
Sales Range | $10 M to 50M |
# of Employees | 72 |
Plant Area |
25,000
ft2
|
Annual Production | 28,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $65,568 | 1,275,200 |
kWh
|
$0.051 |
Electricity Demand | $16,264 | 2,894 |
kW-mo/yr
|
$5.62 |
Electricity Fees | $3,997 | - |
|
- |
Natural Gas | $1,261 | 113 |
MMBtu
|
$11.16 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,336 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,715 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $4,838 | $903 |
$3,353
65,203
kWh
|
$1,259
-
kW-mo/yr
|
$226 | - | - | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $2,621 | $192 |
$2,106
40,948
kWh
|
$393
-
kW-mo/yr
|
$122 | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,009 | $1,200 |
$377
7,323
kWh
|
- | $18 | - | $1,614 | |
04 | 2.7134: Use photocell controls | $590 | $112 |
$411
7,989
kWh
|
$152
-
kW-mo/yr
|
$27 | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $278 | $80 |
$265
5,150
kWh
|
- | $13 | - | - | |
06 | 3.5313: Increase amount of waste recovered for resale | $1,000 | - | - | - | - |
$1,000
-
lb
|
- | |
TOTAL RECOMMENDED | $11,336 | $2,487 |
$6,512
126,613
kWh
|
$1,804
-
kW-mo/yr
|
$406 |
$1,000
-
lb
|
$1,614 | ||
TOTAL IMPLEMENTED | $8,715 | $2,295 |
$4,406
85,665
kWh
|
$1,411
-
kW-mo/yr
|
$284 |
$1,000
-
lb
|
$1,614 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs