Assessment Year | 2003 |
---|---|
Principal Product | Structural and Architectural Metals |
NAICS | 332312: Fabricated Structural Metal Manufacturing |
SIC | 3441: Fabricated Structural Metal |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
100,000
ft2
|
Annual Production | 7,000
ton
|
Production Hrs. Annual | 2,600
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $80,869 | 1,510,312 |
kWh
|
$0.054 |
Electricity Demand | $39,351 | 7,002 |
kW-mo/yr
|
$5.62 |
Electricity Fees | $7,712 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $59,280 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Liquid (haz) Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $9,977 | $945 |
$5,835
108,975
kWh
|
$3,541
-
kW-mo/yr
|
$601 | - | - | |
02 | 2.7134: Use photocell controls | $3,273 | $280 |
$1,918
35,818
kWh
|
$1,158
-
kW-mo/yr
|
$197 | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,190 | $15 |
$1,277
23,855
kWh
|
$781
-
kW-mo/yr
|
$132 | - | - | |
04 | 2.7135: Install occupancy sensors | $746 | $56 |
$437
8,162
kWh
|
$264
-
kW-mo/yr
|
$45 | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $594 | $800 |
$558
10,428
kWh
|
- | $36 | - | - | |
06 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $40,875 | $100,279 | - | - | - |
$40,875
-
gal
|
- | |
07 | 2.8112: Combine utility meters | $1,625 | - | - | - | - | - | $1,625 | |
TOTAL RECOMMENDED | $59,280 | $102,375 |
$10,025
187,238
kWh
|
$5,744
-
kW-mo/yr
|
$1,011 |
$40,875
-
gal
|
$1,625 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Liquid (haz) Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs