Assessment Year 2003
Principal Product Rotating Machinery
NAICS 333611: Turbine and Turbine Generator Set Units Manufacturing
SIC 3511: Steam, Gas, and Hydraulic Turbines, and Turbine Generator Set Units
Sales Range $5
M
to 10
M
# of Employees 35
Plant Area 45,000
ft2
Annual Production 500
pieces
Production Hrs. Annual 4,160
hrs
Location (State) Louisiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $70,296 1,377,231
kWh
Electricity Demand $18,653 3,319
kW-mo/yr
Electricity Fees $4,745 -
Natural Gas $5,588 707
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $25,024 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $5,137

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Personnel Changes Savings
01 2.7243: Improve air circulation with destratification fans / other methods $17,499 $7,098 $17,572
344,275
kWh
- $937 $(-1,010.0)
02 2.7226: Use computer programs to optimize hvac performance $3,785 $880 $3,593
70,400
kWh
- $192 -
03 2.7226: Use computer programs to optimize hvac performance $1,515 $763 - $1,457
-
kW-mo/yr
$58 -
04 2.7134: Use photocell controls $582 $28 $408
7,989
kWh
$152
-
kW-mo/yr
$22 -
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $443 $360 $421
8,251
kWh
- $22 -
06 2.7135: Install occupancy sensors $384 $56 $240
4,692
kWh
$129
-
kW-mo/yr
$15 -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $386 $280 $136
2,663
kWh
- $7 $243
08 4.611: Begin a practice of predictive / preventative maintenance $430 $32 - - - $430
TOTAL RECOMMENDED $25,024 $9,497 $22,370
438,270
kWh
$1,738
-
kW-mo/yr
$1,253 $(-337.0)
TOTAL IMPLEMENTED $5,137 $1,244 $4,377
85,744
kWh
$281
-
kW-mo/yr
$236 $243
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs