Assessment Year | 2003 |
---|---|
Principal Product | Rotating Machinery |
NAICS | 333611: Turbine and Turbine Generator Set Units Manufacturing |
SIC | 3511: Steam, Gas, and Hydraulic Turbines, and Turbine Generator Set Units |
Sales Range | $5 M to 10M |
# of Employees | 35 |
Plant Area |
45,000
ft2
|
Annual Production | 500
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $70,296 | 1,377,231 |
kWh
|
$0.051 |
Electricity Demand | $18,653 | 3,319 |
kW-mo/yr
|
$5.62 |
Electricity Fees | $4,745 | - |
|
- |
Natural Gas | $5,588 | 707 |
MMBtu
|
$7.90 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,024 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,137 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7243: Improve air circulation with destratification fans / other methods | $17,499 | $7,098 |
$17,572
344,275
kWh
|
- | $937 | $(-1,010.0) | |
02 | 2.7226: Use computer programs to optimize hvac performance | $3,785 | $880 |
$3,593
70,400
kWh
|
- | $192 | - | |
03 | 2.7226: Use computer programs to optimize hvac performance | $1,515 | $763 | - |
$1,457
-
kW-mo/yr
|
$58 | - | |
04 | 2.7134: Use photocell controls | $582 | $28 |
$408
7,989
kWh
|
$152
-
kW-mo/yr
|
$22 | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $443 | $360 |
$421
8,251
kWh
|
- | $22 | - | |
06 | 2.7135: Install occupancy sensors | $384 | $56 |
$240
4,692
kWh
|
$129
-
kW-mo/yr
|
$15 | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $386 | $280 |
$136
2,663
kWh
|
- | $7 | $243 | |
08 | 4.611: Begin a practice of predictive / preventative maintenance | $430 | $32 | - | - | - | $430 | |
TOTAL RECOMMENDED | $25,024 | $9,497 |
$22,370
438,270
kWh
|
$1,738
-
kW-mo/yr
|
$1,253 | $(-337.0) | ||
TOTAL IMPLEMENTED | $5,137 | $1,244 |
$4,377
85,744
kWh
|
$281
-
kW-mo/yr
|
$236 | $243 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs