Assessment Year | 2003 |
---|---|
Principal Product | Gasoline |
NAICS | 324191: Petroleum Lubricating Oil and Grease Manufacturing |
SIC | 2992: Lubricating Oils and Greases |
Sales Range | greater than $500 M |
# of Employees | 249 |
Plant Area |
12
ft2
|
Annual Production | 29,200,000
bbl
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $4,468,988 | 102,540,253 |
kWh
|
$0.044 |
Electricity Fees | $174,291 | - |
|
- |
Natural Gas | $2,560,523 | 535,303 |
MMBtu
|
$4.78 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $879,604 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $502,957 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $390,733 | $195,000 | - | - |
$390,733
-
MMBtu
|
- | |
02 | 2.1115: Eliminate combustible gas in flue gas | $197,664 | $250,000 | - | - |
$197,664
-
MMBtu
|
- | |
03 | 2.2511: Insulate bare equipment | $101,833 | $7,757 | - | - |
$101,833
-
MMBtu
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $87,485 | $28,240 |
$84,201
1,926,796
kWh
|
$3,284 | - | - | |
05 | 2.3321: Use steam pressure reduction to generate power | $65,820 | $312,701 |
$166,140
3,801,840
kWh
|
$6,479 |
$(-106,799.0)
-
MMBtu
|
- | |
06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $21,972 | $5,600 | - | - |
$21,972
-
MMBtu
|
- | |
07 | 2.2511: Insulate bare equipment | $5,380 | $682 | - | - |
$5,380
-
MMBtu
|
- | |
08 | 2.7134: Use photocell controls | $3,809 | $1,176 |
$3,666
83,886
kWh
|
$143 | - | - | |
09 | 2.8123: Pay utility bills on time | $2,767 | $30 | - | $2,767 | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,141 | $1,050 |
$896
20,498
kWh
|
$35 | - | $1,210 | |
TOTAL RECOMMENDED | $879,604 | $802,236 |
$254,903
5,833,020
kWh
|
$12,708 |
$610,783
-
MMBtu
|
$1,210 | ||
TOTAL IMPLEMENTED | $502,957 | $228,870 |
$84,201
1,926,796
kWh
|
$6,051 |
$412,705
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs