Assessment Year | 2003 |
---|---|
Principal Product | Pump fabrication |
NAICS | 333911: Pump and Pumping Equipment Manufacturing |
SIC | 3561: Pumps and Pumping Equipment |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
253,952
ft2
|
Annual Production | 150,000
pieces
|
Production Hrs. Annual | 7,000
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $143,949 | 5,297,292 |
kWh
|
$0.027 |
Electricity Demand | $93,762 | 10,797 |
kW-mo/yr
|
$8.68 |
Electricity Fees | $27,946 | - |
|
- |
Natural Gas | $65,959 | 12,058 |
MMBtu
|
$5.47 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $33,571 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,479 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7134: Use photocell controls | $8,239 | $1,196 | - | - | $512 |
$7,727
-
MMBtu
|
- | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $6,916 | $900 |
$3,760
138,232
kWh
|
$2,433
-
kW-mo/yr
|
$723 | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,845 | $4,800 |
$6,128
225,304
kWh
|
- | $717 | - | - | |
04 | 2.7135: Install occupancy sensors | $5,699 | $280 |
$3,140
115,439
kWh
|
$1,962
-
kW-mo/yr
|
$597 | - | - | |
05 | 2.7134: Use photocell controls | $1,257 | $1,784 |
$1,125
41,342
kWh
|
- | $132 | - | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $981 | $20 |
$574
21,099
kWh
|
$304
-
kW-mo/yr
|
$103 | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $488 | $240 |
$149
5,466
kWh
|
- | $17 | - | $322 | |
08 | 4.611: Begin a practice of predictive / preventative maintenance | $3,146 | $1,157 | - | - | - | - | $3,146 | |
TOTAL RECOMMENDED | $33,571 | $10,377 |
$14,876
546,882
kWh
|
$4,699
-
kW-mo/yr
|
$2,801 |
$7,727
-
MMBtu
|
$3,468 | ||
TOTAL IMPLEMENTED | $10,479 | $6,197 |
$6,277
230,770
kWh
|
- | $734 | - | $3,468 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs