ITAC Assessment: LL0162
ITAC logo
ITAC Assessment: LL0162
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2003
Principal Product Bread
NAICS 311812: Commercial Bakeries
SIC 2051: Bread and Other Bakery Products, Except Cookies and Crackers
Sales Range $10
M
to 50
M
# of Employees 166
Plant Area 130,000
ft2
Annual Production 53,000,000
lb
Production Hrs. Annual 7,280
hrs
Location (State) Louisiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $362,065 7,794,392
kWh
Electricity Demand $79,158 14,085
kW-mo/yr
Electricity Fees $24,268 -
Natural Gas $150,821 31,563
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $59,822 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $37,445

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Solid Waste (non-haz) Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $15,597 $4,620 $14,997
322,857
kWh
- $600 -
02 2.7111: Reduce illumination to minimum necessary levels $11,299 $855 $10,027
215,870
kWh
$837
-
kW-mo/yr
$435 -
03 2.4239: Eliminate or reduce compressed air usage $7,812 $683 $7,512
161,728
kWh
- $300 -
04 2.4231: Reduce the pressure of compressed air to the minimum required $7,770 - $6,206
133,612
kWh
$1,265
-
kW-mo/yr
$299 -
05 2.3212: Optimize plant power factor $2,099 $2,310 - $2,018
-
kW-mo/yr
$81 -
06 2.7134: Use photocell controls $938 $82 $370
7,957
kWh
$90
-
kW-mo/yr
$478 -
07 2.7135: Install occupancy sensors $229 $205 $164
3,523
kWh
$56
-
kW-mo/yr
$9 -
08 3.5313: Increase amount of waste recovered for resale $14,078 $3,120 - - - $14,078
-
lb
TOTAL RECOMMENDED $59,822 $11,875 $39,276
845,547
kWh
$4,266
-
kW-mo/yr
$2,202 $14,078
-
lb
TOTAL IMPLEMENTED $37,445 $7,740 $21,203
456,469
kWh
$1,265
-
kW-mo/yr
$899 $14,078
-
lb
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Solid Waste (non-haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs