Assessment Year | 2003 |
---|---|
Principal Product | Oilfield Equipment |
NAICS | 333132: Oil and Gas Field Machinery and Equipment Manufacturing |
SIC | 3533: Oil and Gas Field Machinery and Equipment |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
70,000
ft2
|
Annual Production | 21,000
pieces
|
Production Hrs. Annual | 5,824
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $296,629 | 4,492,372 |
kWh
|
$0.066 |
Electricity Demand | $4,788 | 848 |
kW-mo/yr
|
$5.65 |
Electricity Fees | $13,592 | - |
|
- |
Natural Gas | $23,058 | 5,685 |
MMBtu
|
$4.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $98,092 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Consumption Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7134: Use photocell controls | $50,631 | $4,551 |
$48,684
736,969
kWh
|
- | $1,947 | - | - | - | |
02 | 2.7135: Install occupancy sensors | $17,563 | $5,075 |
$16,890
255,673
kWh
|
- | $673 | - | - | - | |
03 | 2.7232: Replace existing hvac unit with high efficiency model | $4,307 | $10,605 | - | - | - |
$4,307
-
MMBtu
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,909 | $1,360 |
$4,721
71,463
kWh
|
- | $188 | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,798 | $900 |
$660
9,986
kWh
|
$79
-
kW-mo/yr
|
$30 | - | - | $1,029 | |
06 | 2.8112: Combine utility meters | $15,037 | - | - | - | $15,037 | - | - | - | |
07 | 4.611: Begin a practice of predictive / preventative maintenance | $1,928 | $786 | - | - | - | - | - | $1,928 | |
08 | 2.8112: Combine utility meters | $1,163 | - | - | - | - | - |
$1,163
-
Tgal
|
- | |
09 | 2.8112: Combine utility meters | $756 | - | - | - | - |
$756
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $98,092 | $23,277 |
$70,955
1,074,091
kWh
|
$79
-
kW-mo/yr
|
$17,875 |
$5,063
-
MMBtu
|
$1,163
-
Tgal
|
$2,957 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Consumption Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs