Assessment Year | 2003 |
---|---|
Principal Product | HFCs |
NAICS | 325998: All Other Miscellaneous Chemical Product and Preparation Manufacturing |
SIC | 2819: Industrial Inorganic Chemicals, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
208,000
ft2
|
Annual Production | 39,000
ton
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $3,780,874 | 121,581,962 |
kWh
|
$0.031 |
Electricity Demand | $2,301,415 | 208,089 |
kW-mo/yr
|
$11.06 |
Electricity Fees | $313,319 | - |
|
- |
Natural Gas | $7,233,842 | 1,515,791 |
MMBtu
|
$4.77 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $588,896 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $246,886 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3321: Use steam pressure reduction to generate power | $336,249 | $481,633 |
$671,319
11,151,480
kWh
|
- | - |
$(-335,070.0)
-
MMBtu
|
- | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $217,796 | $12,400 | - | - | - |
$217,796
-
MMBtu
|
- | |
03 | 2.7134: Use photocell controls | $19,066 | $924 |
$8,609
276,827
kWh
|
$9,523
-
kW-mo/yr
|
$934 | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,635 | $20 |
$3,368
108,296
kWh
|
$1,991
-
kW-mo/yr
|
$276 | - | - | |
05 | 2.7135: Install occupancy sensors | $4,821 | $1,204 |
$1,897
60,985
kWh
|
$2,688
-
kW-mo/yr
|
$236 | - | - | |
06 | 2.2511: Insulate bare equipment | $4,389 | $642 | - | - | - |
$4,389
-
MMBtu
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $940 | $525 |
$319
10,249
kWh
|
- | $16 | - | $605 | |
TOTAL RECOMMENDED | $588,896 | $497,348 |
$685,512
11,607,837
kWh
|
$14,202
-
kW-mo/yr
|
$1,462 |
$(-112,885.0)
-
MMBtu
|
$605 | ||
TOTAL IMPLEMENTED | $246,886 | $13,986 |
$11,977
385,123
kWh
|
$11,514
-
kW-mo/yr
|
$1,210 |
$222,185
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs