Assessment Year | 2003 |
---|---|
Principal Product | Chemicals |
NAICS | 325110: Petrochemical Manufacturing |
SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
Sales Range | greater than $500 M |
# of Employees | 1,400 |
Plant Area |
72,000,000
ft2
|
Annual Production | 7,200,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $29,219,392 | 1,219,985,200 |
kWh
|
$0.024 |
Electricity Demand | $13,356,917 | 1,814,684 |
kW-mo/yr
|
$7.36 |
Electricity Fees | $44,504 | - |
|
- |
Natural Gas | $52,697,885 | 18,519,383 |
MMBtu
|
$2.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $36,804,695 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $109,742 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $18,488,939 | $413,700 | n/a | - | - | - |
$18,488,939
-
MMBtu
|
- |
02 | 2.2121: Increase amount of condensate returned | $11,340,034 | $773,535 | n/a | - | - | - |
$9,187,645
-
MMBtu
|
$2,152,389
-
gal
|
03 | 2.1336: Install equipment to utilize waste fuel | $6,313,507 | $750,000 | - | - | - |
$6,313,507
-
MMBtu
|
- | |
04 | 2.2162: Reduce excess steam bleeding | $504,716 | $45,360 | - | - | - |
$504,716
-
MMBtu
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $109,742 | $60,716 |
$105,521
4,405,868
kWh
|
- | $4,221 | - | - | |
06 | 2.7134: Use photocell controls | $36,675 | $4,100 |
$24,504
1,023,120
kWh
|
$10,760
-
kW-mo/yr
|
$1,411 | - | - | |
07 | 2.2511: Insulate bare equipment | $11,082 | $2,865 | - | - | - |
$11,082
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $36,804,695 | $2,050,276 |
$130,025
5,428,988
kWh
|
$10,760
-
kW-mo/yr
|
$5,632 |
$34,505,889
-
MMBtu
|
$2,152,389
-
gal
|
||
TOTAL IMPLEMENTED | $109,742 | $60,716 |
$105,521
4,405,868
kWh
|
- | $4,221 | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Other Liquid (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs