Assessment Year | 2002 |
---|---|
Principal Product | Plastic dinnerware |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 250 |
Plant Area |
143,523
ft2
|
Annual Production | 600,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $429,213 | 13,568,600 |
kWh
|
$0.032 |
Electricity Demand | $121,358 | 22,065 |
kW-mo/yr
|
$5.50 |
Electricity Fees | $22,023 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,193 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,920 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $6,310 | $10,850 | - |
$6,067
-
kW-mo/yr
|
$243 | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,890 | $2,580 |
$5,663
179,045
kWh
|
- | $227 | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $2,680 | - |
$2,038
64,428
kWh
|
$539
-
kW-mo/yr
|
$103 | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $1,286 | - |
$978
30,925
kWh
|
$259
-
kW-mo/yr
|
$49 | - | |
05 | 2.7134: Use photocell controls | $205 | $52 |
$109
3,436
kWh
|
$88
-
kW-mo/yr
|
$8 | - | |
06 | 2.7134: Use photocell controls | $102 | $41 |
$54
1,718
kWh
|
$44
-
kW-mo/yr
|
$4 | - | |
07 | 4.611: Begin a practice of predictive / preventative maintenance | $1,720 | $2,400 | - | - | - | $1,720 | |
TOTAL RECOMMENDED | $18,193 | $15,923 |
$8,842
279,552
kWh
|
$6,997
-
kW-mo/yr
|
$634 | $1,720 | ||
TOTAL IMPLEMENTED | $13,920 | $15,830 |
$5,663
179,045
kWh
|
$6,067
-
kW-mo/yr
|
$470 | $1,720 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs