| Assessment Year | 2002 |
|---|---|
| Principal Product | Salt |
| NAICS |
n/a
|
| SIC | 2899: Chemicals and Chemical Preparations, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 49 |
| Plant Area |
7,000,000
ft2
|
| Annual Production | 230,000
ton
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $788,886 | 14,170,043 |
kWh
|
$0.056 |
| Electricity Demand | $264,340 | 30,274 |
kW-mo/yr
|
$8.73 |
| Electricity Fees | $(-83,161.0) | - |
|
- |
| Natural Gas | $1,961,401 | 440,603 |
MMBtu
|
$4.45 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $895,442 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $79,426 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3412: Use waste heat to produce steam to drive a steam turbine-generator | $546,668 | $991,085 |
$822,162
14,851,200
kWh
|
- | $21,026 |
$(-296,520.0)
-
MMBtu
|
|
| 02 | 2.2414: Use waste heat from hot flue gases to preheat | $225,040 | $57,600 | - | - | $8,655 |
$216,385
-
MMBtu
|
|
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $36,016 | $13,170 |
$34,631
625,560
kWh
|
- | $1,385 | - | |
| 04 | 2.3212: Optimize plant power factor | $35,735 | $32,655 | - |
$34,361
-
kW-mo/yr
|
$1,374 | - | |
| 05 | 3.4154: Eliminate leaks in water lines and valves | $11,865 | $3,600 |
$11,409
205,165
kWh
|
- | $456 | - | |
| 06 | 2.2511: Insulate bare equipment | $9,698 | $1,016 | - | - | $373 |
$9,325
-
MMBtu
|
|
| 07 | 2.2511: Insulate bare equipment | $8,850 | $1,326 | - | - | $340 |
$8,510
-
MMBtu
|
|
| 08 | 2.2511: Insulate bare equipment | $8,388 | $2,540 | - | - | $323 |
$8,065
-
MMBtu
|
|
| 09 | 2.7134: Use photocell controls | $5,775 | $960 |
$3,877
69,713
kWh
|
$1,676
-
kW-mo/yr
|
$222 | - | |
| 10 | 2.2511: Insulate bare equipment | $3,301 | $957 | - | - | $127 |
$3,174
-
MMBtu
|
|
| 11 | 2.7134: Use photocell controls | $2,798 | $369 |
$2,140
38,488
kWh
|
$550
-
kW-mo/yr
|
$108 | - | |
| 12 | 2.7111: Reduce illumination to minimum necessary levels | $1,154 | $300 |
$527
9,485
kWh
|
$583
-
kW-mo/yr
|
$44 | - | |
| 13 | 2.2511: Insulate bare equipment | $154 | $102 | - | - | $6 |
$148
-
MMBtu
|
|
| TOTAL RECOMMENDED | $895,442 | $1,105,680 |
$874,746
15,799,611
kWh
|
$37,170
-
kW-mo/yr
|
$34,439 |
$(-50,913.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $79,426 | $23,011 |
$46,567
840,210
kWh
|
$583
-
kW-mo/yr
|
$3,054 |
$29,222
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs