Assessment Year | 2002 |
---|---|
Principal Product | Ceramic Pellets |
NAICS |
n/a
|
SIC | 3299: Nonmetallic Mineral Products, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 50 |
Plant Area |
174,239
ft2
|
Annual Production | 100,000,000
lb
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $533,794 | 12,263,962 |
kWh
|
$0.044 |
Electricity Demand | $153,945 | 20,810 |
kW-mo/yr
|
$7.40 |
Electricity Fees | $28,799 | - |
|
- |
Natural Gas | $1,178,453 | 199,986 |
MMBtu
|
$5.89 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $302,147 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $269,865 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1125: Convert to oxyfuel burners | $235,855 | $281,796 | - | - | - |
$235,855
-
MMBtu
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $20,887 | $93,094 |
$20,083
441,869
kWh
|
- | $804 | - | - | |
03 | 2.3212: Optimize plant power factor | $32,031 | $38,570 | - |
$30,799
-
kW-mo/yr
|
$1,232 | - | - | |
04 | 2.7134: Use photocell controls | $251 | $128 | - |
$81
-
kW-mo/yr
|
$10 |
$160
-
MMBtu
|
- | |
05 | 2.8114: Change rate schedules or other changes in utility service | $13,123 | - | - | - | - | - |
$13,123
-
Tgal
|
|
TOTAL RECOMMENDED | $302,147 | $413,588 |
$20,083
441,869
kWh
|
$30,880
-
kW-mo/yr
|
$2,046 |
$236,015
-
MMBtu
|
$13,123
-
Tgal
|
||
TOTAL IMPLEMENTED | $269,865 | $374,890 |
$20,083
441,869
kWh
|
- | $804 |
$235,855
-
MMBtu
|
$13,123
-
Tgal
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs